{"id":503,"date":"2017-09-11T09:58:23","date_gmt":"2017-09-11T09:58:23","guid":{"rendered":"http:\/\/www.pucsl.gov.lk\/www-2\/?page_id=503"},"modified":"2018-01-03T09:27:52","modified_gmt":"2018-01-03T03:57:52","slug":"distance-from-buildings-or-structures-to-overhead-lines","status":"publish","type":"page","link":"https:\/\/www.pucsl.gov.lk\/si\/electricity\/safety\/distance-from-buildings-or-structures-to-overhead-lines\/","title":{"rendered":"\u0dc0\u0dd2\u0daf\u0dd4\u0dbd\u0dd2 \u0dbb\u0dd0\u0dc4\u0dd0\u0db1\u0dca \u0d9c\u0ddc\u0da9\u0db1\u0dd0\u0d9c\u0dd2\u0dbd\u0dd2 \u0d85\u0dad\u0dbb \u0db4\u0dbb\u0dad\u0dbb\u0dba"},"content":{"rendered":"<p>&nbsp;<\/p>\n<p>Minimum distances from any building or structure to any position to which a conductor in an overhead line may swing under the influence of wind shall be as specified below<\/p>\n<p>&nbsp;<\/p>\n<table>\n<tbody>\n<tr>\n<td width=\"218\"><strong>Nominal Voltages<\/strong><\/td>\n<td width=\"222\"><strong>Vertical Distance<\/strong><\/td>\n<td width=\"198\"><strong>Horizontal Distance<\/strong><\/td>\n<\/tr>\n<tr>\n<td width=\"218\">Not exceeding 1000 Volts<\/td>\n<td width=\"222\">2.40 m<\/td>\n<td width=\"198\">1.50 m<\/td>\n<\/tr>\n<tr>\n<td width=\"218\">Exceeding 1000 Volts but not exceeding 11,000 Volts<\/td>\n<td width=\"222\">2.70 m<\/td>\n<td width=\"198\">1.50 m<\/td>\n<\/tr>\n<tr>\n<td width=\"218\">Exceeding 11,000 Volts but not exceeding 33,000 Volts<\/td>\n<td width=\"222\">3.00 m<\/td>\n<td width=\"198\">2.00 m<\/td>\n<\/tr>\n<tr>\n<td width=\"218\">Exceeding 33,000 Volts but not exceeding 132,000 Volts<\/td>\n<td width=\"222\">4.10 m<\/td>\n<td width=\"198\">4.10 m<\/td>\n<\/tr>\n<tr>\n<td width=\"218\">Exceeding 132,000 Volts but not exceeding 220,000 Volts<\/td>\n<td width=\"222\">5.18 m<\/td>\n<td width=\"198\">5.18 m<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>&nbsp;<\/p>\n<p>The regulation also specifies the limits of the height above the ground that should have between an overhead line is over or along a road or over any other location accessible or inaccessible to vehicular traffic.<\/p>\n","protected":false},"excerpt":{"rendered":"<p>&nbsp; Minimum distances from any building or structure to any position to which a conductor in an overhead line may swing under the influence of wind shall be as specified below &nbsp; Nominal Voltages Vertical Distance Horizontal Distance Not exceeding 1000 Volts 2.40 m 1.50 m Exceeding 1000 Volts but not exceeding 11,000 Volts 2.70 [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":0,"parent":53,"menu_order":0,"comment_status":"closed","ping_status":"closed","template":"page-wysiwyg.php","meta":{"ngg_post_thumbnail":0},"_links":{"self":[{"href":"https:\/\/www.pucsl.gov.lk\/si\/wp-json\/wp\/v2\/pages\/503"}],"collection":[{"href":"https:\/\/www.pucsl.gov.lk\/si\/wp-json\/wp\/v2\/pages"}],"about":[{"href":"https:\/\/www.pucsl.gov.lk\/si\/wp-json\/wp\/v2\/types\/page"}],"author":[{"embeddable":true,"href":"https:\/\/www.pucsl.gov.lk\/si\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/www.pucsl.gov.lk\/si\/wp-json\/wp\/v2\/comments?post=503"}],"version-history":[{"count":5,"href":"https:\/\/www.pucsl.gov.lk\/si\/wp-json\/wp\/v2\/pages\/503\/revisions"}],"predecessor-version":[{"id":1989,"href":"https:\/\/www.pucsl.gov.lk\/si\/wp-json\/wp\/v2\/pages\/503\/revisions\/1989"}],"up":[{"embeddable":true,"href":"https:\/\/www.pucsl.gov.lk\/si\/wp-json\/wp\/v2\/pages\/53"}],"wp:attachment":[{"href":"https:\/\/www.pucsl.gov.lk\/si\/wp-json\/wp\/v2\/media?parent=503"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}